◆Gunakake Ketentuan
Dhuwur: ≤2000m;
Suhu udara sekitar: -45 ℃ ~ + 50 ℃;
Kelembapan relatif: rata-rata saben dina ≤95%, rata-rata saben wulan ≤90%;
Ora cocog kanggo instalasi sing ana getaran sing kerep lan abot, uap banyu, gas, celengan korosif kimia, semprotan uyah, bledug lan rereget, lan instalasi bebaya geni lan bledosan sing jelas mengaruhi kinerja mekanisme kasebut.
Tekanan gas SF6 sing dirating yaiku 0.04MPa, lan gas SF6 memenuhi syarat GB / T 12022-2014 "Industri SF6".
◆ Parameter Teknis Utama
NO. | barang | Unit | Nilai |
1 | Dirating voltase | kV | 12 |
2 | Frekuensi dirating | Hz | 50 |
3 | Rated saiki | A | 630 |
4 | Dirating wektu cendhak tahan saiki | kA | 20, 25 |
5 | Rated puncak tahan saiki | kA | 50 |
6 | Dirating short circuit duration | S | 4 |
7 | Rated short circuit nggawe saiki | kA | 50 |
8 | Operasi teoretis | kaping | 10000 |
9 | Resistance sirkuit utama | mΩ | ≤60 |
10 | 1 min frekuensi daya tahan voltase | kV | 38 (ing udara) |
◆Sakabèhé Dimensi