Interrupter vakum kanggo saklar pemutus beban TF-12/630-20 (2F56)

Katrangan singkat:


Detail Produk

Tag produk

sdg

 

Spesifikasi Teknis Utama

Tegangan Rated

KV

12

Rated Saiki

A

630

Frekuensi Rated

Hz

50

Wektu cendhak Daya-frekuensi Tahan Tegangan (1 menit)

KV

42

Rated Lightning Impulse Tahan Tegangan (Puncak)

KV

75

Rated Peak Tahan Saiki

THE

50

Dirating Short-circuit Nggawe Saiki

THE

50

Dirating Short-wektu Tahan Saiki

THE

20

Dirating Duration saka Short-circ

S

4

Rated Closed-loop Breaking Saiki

A

630

Dirating Kapasitas saka Transformer ora mbukak

A

Arus Transformasi Tanpa Beban

Kanthi Kapasitas 1250kVA

Rated Kabel-ngisi daya Breaking Saiki

A

10

Rated Transfer Saiki

A

3150

Massa Parts Obah

Kg

0.5

Ketahanan Mekanik

kaping

10000

Kontak Ditutup Force Amarga Bellows lan Atmosfer

N

80±30

Counterforce saka Kontak ing Full Stroke

N

130±30

Resistance Circuit ing Min.Rated Kontak Force

Kontak Limit Erosi

mm

3

Panyimpenan Urip

taun

20

Data Mekanik Saklar Vakum Dilengkapi Interrupters

Clearance Antarane Bukak Kontak

mm

9±1

Rata-rata Kacepetan Opening

m/s

1.0±0.2

Rata-rata Kacepetan Panutup

m/s

0,6±0,2

Rated Tekanan Kontak

N

900±200

Durasi Bounce Kontak nalika Tutup Operasi

ms

Metu saka Simultaneity saka Tutup lan Operasi Kontak

ms

Maksimum Rebound Sajrone Opening

mm

2

Cathetan

1. Meet utawa ngluwihi syarat toleransi electrical saka kelas E2 kanggo autoreclosing tugas saben IEC62271-100 lan GB1984-2003.

2. Dirating karakteristik tobe givenon request.

3. Nilai insulasi sing dirating mbutuhake insulasi ekstemal, kayata Sf6, lenga utawa bahan dielektrik padhet lsp.