Parameter Teknis Utama
ZN12-12
Ora | Item | Unit | Nilai | ||||
1 | Dirating voltase | kV | |||||
2 | Rated saiki | A | 630, 1250, 1600 | 1250, 1600,2000, 2500,3150 | 2000, 2500, 3150,4000 | ||
3 | Rated short circuit breaking saiki | kA | 20 | 25 | 31.5 | 40 | 50 |
4 | Arus stabilitas dinamis (puncak) | kA | 50 | 63 | 80 | 100 | 125 |
5 | 4s saiki stabilitas termal | kA | 20 | 25 | 31.5 | 40/3s | 50/3s |
6 | Rated short circuit nggawe saiki | kA | 50 | 63 | 80 | 100 | 125 |
7 | Nomer pemutus arus hubung singkat | kaping | 30 | 12 | |||
8 | Rated urutan operasi | CO-0.3S-CO-180S-CO | O-180S-CO-180S-CO | ||||
9 | Urip mekanik | kaping | 10000 | 6000 | |||
10 | Dirating nomer breaking saiki | kaping | 10000 | 6000 | |||
11 | Rated lightning impulse tahan voltase (gelombang lengkap) | kV | 75 | ||||
12 | Dirating frekuensi daya wektu cendhak tahan saiki (1 min) | kV | 42 | ||||
13 | wektu nutup | ms | ≤75 | ||||
14 | wektu mbukak | ms | ≤65 | ||||
15 | Daya lan dirating voltase saka motor panyimpenan energi | W/V | 275W/110V, 220V | ||||
16 | Wektu panyimpenan energi | s |
|
Ora | Item | Unit | Nilai |
17 | Dirating voltase saka nutup coil | ING | 110V, 220V |
18 | Dirating voltase saka mbukak coil | ING | |
19 | Dirating voltase saka interlock coil | ING | |
20 | Rated saiki release | A | 5 |
rong puluh siji | Rated saiki saklar tambahan | A | AC10A, DC5A |
ZN12-40.5
Ora | Item | Unit | Nilai | |
1 | Dirating voltase | kV | 40.5 | |
2 | Rated saiki | A | 1250, 1600, 2000 | 1250, 1600,2000,2500 |
3 | Rated short circuit breaking saiki | kA | 20, 25 | 31.5 |
4 | Arus stabilitas dinamis (puncak) | kA | 50, 63 | 80 |
5 | 4s saiki stabilitas termal | kA | 20, 25 | 31.5 |
6 | Rated short circuit nggawe arus (puncak) | kA | 50, 63 | 80 |
7 | Nomer pemutus arus hubung singkat | kaping | 30 | 20 |
8 | Rated urutan operasi | CO-0.3S-CO-180S-CO | ||
9 | Rated lightning impulse tahan voltase (gelombang lengkap) | kV | 180 | |
10 | Dirating frekuensi daya wektu cendhak tahan saiki (1 min) | kV | 95 | |
11 | wektu nutup | ms | ≤90 | |
12 | wektu mbukak | ms | ≤75 | |
13 | Mekanik! urip | kaping | 10000 | 60000 |
14 | Dirating nomer breaking saiki | kaping | 10000 | 60000 |
15 | Rated kapasitor bank breaking saiki | A | 630 | |
Daya motor panyimpenan energi | ING | 275 | ||
17 | Dirating voltase saka motor panyimpenan energi | ING | ≃110V, 220V | |
18 | Wektu panyimpenan energi | s | ≤15 | |
19 | Dirating voltase saka nutup lan mbukak kumparan | ING | ≃110V, 220V | |
20 | Rated saiki release overcurrent | A | 5 | |
rong puluh siji | Rated saiki saklar tambahan | A | AC10A, DC5A |
Gambar Struktur Umum lan Ukuran Instalasi (unit: mm)
♦ZN12-12 (dipasang miring)
Cathetan: ukuran 360mm kanggo saiki ing ndhuwur 2000A, ing ngisor 2000A, ukurane 350mm.
Wigati, ing gambar, (215) tegese nalika L3 = 516mm, ukurane 215mm.
Ing 1600A: bolongan terminal stopkontak ndhuwur lan ngisor 2-M12
Ndhuwur 2000A: bolongan terminal stopkontak ndhuwur lan ngisor 4-M12
Jinis | L | L1 | L2 | L3 | pangandikan |
ZN12-12 | 210 | 586 | 610 | 516 | Kanthi partisi antar fase |
230 | 620 | 650 | 565 | ||
250 | 700 | 740 | 565 | ||
275 | 696 | 720 | 516 |
♦ZN12-12B (dipasang flush)(569575)
Cathetan: (575) lan (364) tegese nalika arus patah hubung singkat 40kA utawa luwih dhuwur, ukurane 575mm, 364mm.
Lubang terminal stopkontak ndhuwur lan ngisor 4-M12
Cathetan: (215) tegese nalika L3=516mm;ukuran 215 mm.
Jinis | L | L1 | L2 | L3 |
ZN12-12B | 210 | 586 | 610 | 516 |
230 | 620 | 650 | 565 | |
250 | 700 | 740 | 565 | |
275 | 696 | 720 | 516 |
Cathetan Kanthi partisi antar fase