ZN12-12 / 40.5 Series Indoor High Voltage Vacuum Breaker

Katrangan singkat:


Detail Produk

Tag produk

ZN12-12 / 40.5 njero ruangan HV vakum sirkuit mbobol punika 3-phase AC 50Hz 12kV / 40.5KV peralatan ngalih njero ruangan.

♦ Cara instalasi: jinis withdrawable, jinis tetep;

♦ Mekanisme operasi: mekanisme rating spring ope;

♦ Aplikasi: switchgear GBC-35, JYN1-35.

 

Kondisi Lingkungan

♦ Suhu sekitar: -25°C~+40°C;

♦ Dhuwur:

♦ Kelembapan relatif: rata-rata saben dina ;

♦ Intensitas lindhu:

♦ Panggonan tanpa geni, bebaya bledosan, reged serius, korosi kimia, uga geter kuat.

 

Parameter Teknis Utama

ZN12-12

Ora Item

Unit

Nilai

1 Dirating voltase

kV

2 Rated saiki

A

630, 1250, 1600

1250, 1600,2000,

2500,3150

2000, 2500,

3150,4000

3 Rated short circuit breaking saiki

kA

20

25

31.5

40

50

4 Arus stabilitas dinamis (puncak)

kA

50

63

80

100

125

5 4s saiki stabilitas termal

kA

20

25

31.5

40/3s

50/3s

6 Rated short circuit nggawe saiki

kA

50

63

80

100

125

7 Nomer pemutus arus hubung singkat kaping

30

12

8 Rated urutan operasi

CO-0.3S-CO-180S-CO

O-180S-CO-180S-CO

9 Urip mekanik kaping

10000

6000

10 Dirating nomer breaking saiki kaping

10000

6000

11 Rated lightning impulse tahan voltase (gelombang lengkap)

kV

75

12 Dirating frekuensi daya wektu cendhak tahan saiki (1 min)

kV

42

13 wektu nutup

ms

≤75

14 wektu mbukak

ms

≤65

15 Daya lan dirating voltase saka motor panyimpenan energi

W/V

275W/110V, 220V

16 Wektu panyimpenan energi

s

 

Ora

Item

Unit

Nilai

17 Dirating voltase saka nutup coil

ING

110V, 220V

18 Dirating voltase saka mbukak coil

ING

19 Dirating voltase saka interlock coil

ING

20 Rated saiki release

A

5

rong puluh siji Rated saiki saklar tambahan

A

AC10A, DC5A

ZN12-40.5

Ora Item

Unit

Nilai

1 Dirating voltase

kV

40.5

2 Rated saiki

A

1250, 1600,

2000

1250, 1600,2000,2500
3 Rated short circuit breaking saiki

kA

20, 25

31.5
4 Arus stabilitas dinamis (puncak)

kA

50, 63

80
5 4s saiki stabilitas termal

kA

20, 25

31.5
6 Rated short circuit nggawe arus (puncak)

kA

50, 63

80
7 Nomer pemutus arus hubung singkat kaping

30

20
8 Rated urutan operasi

CO-0.3S-CO-180S-CO

9 Rated lightning impulse tahan voltase (gelombang lengkap)

kV

180

10 Dirating frekuensi daya wektu cendhak tahan saiki (1 min)

kV

95

11

wektu nutup

ms

≤90

12 wektu mbukak

ms

≤75

13 Mekanik! urip kaping

10000

60000
14 Dirating nomer breaking saiki kaping

10000

60000
15 Rated kapasitor bank breaking saiki

A

630

Daya motor panyimpenan energi

ING

275

17 Dirating voltase saka motor panyimpenan energi

ING

≃110V, 220V

18

Wektu panyimpenan energi

s

≤15

19

Dirating voltase saka nutup lan mbukak kumparan

ING

≃110V, 220V

20

Rated saiki release overcurrent

A

5

rong puluh siji

Rated saiki saklar tambahan

A

AC10A, DC5A

 

Gambar Struktur Umum lan Ukuran Instalasi (unit: mm)

ZN12-12 (dipasang miring)

rht (1)

Cathetan: ukuran 360mm kanggo saiki ing ndhuwur 2000A, ing ngisor 2000A, ukurane 350mm.

rht (2)

Wigati, ing gambar, (215) tegese nalika L3 = 516mm, ukurane 215mm.

Ing 1600A: bolongan terminal stopkontak ndhuwur lan ngisor 2-M12

Ndhuwur 2000A: bolongan terminal stopkontak ndhuwur lan ngisor 4-M12

Jinis

L

L1

L2

L3

pangandikan

ZN12-12

210

586

610

516

Kanthi partisi antar fase

230

620

650

565

250

700

740

565

275

696

720

516

ZN12-12B (dipasang flush)(569575)

svd

Cathetan: (575) lan (364) tegese nalika arus patah hubung singkat 40kA utawa luwih dhuwur, ukurane 575mm, 364mm.

punika

Lubang terminal stopkontak ndhuwur lan ngisor 4-M12

Cathetan: (215) tegese nalika L3=516mm;ukuran 215 mm.

Jinis

L

L1

L2

L3

ZN12-12B

210

586

610

516

230

620

650

565

250

700

740

565

275

696

720

516

Cathetan Kanthi partisi antar fase


  • Sadurunge:
  • Sabanjure: