◆ Gunakake Ketentuan
1.Suhu sekitar: -30 ℃ ~ + 60 ℃;
2. Altitude: ≤3000m;
3. Kacepetan angin: ≤34m/s;
4. Kelas polusi: ≤IV.
5. Suhu panyimpenan: -40 ℃ ~ + 85 ℃.
◆ Parameter Teknis Utama
NO. | barang | Unit | Nilai |
1 | voltase dirating | kV | 40.5 |
2 | 1 min frekuensi daya tahan voltase | kV | 95 |
3 | impuls kilat tahan voltase | kV | 185 |
4 | frekuensi dirating | Hz | 50 |
5 | dirating saiki | A | 630.1250.1600 |
6 | dirating short circuit breaking saiki | kA | 20, 25, 31.5 |
7 | arus hubung singkat (puncak) | kA | 50, 63, 80 |
8 | dirating puncak tahan saiki | kA | 50, 63, 80 |
9 | 4s tahan saiki | kA | 20, 25, 31.5 |
10 | urutan operasi dirating | S | O-0.1s-CO-3s-CO-6S-60s Recovery |
11 | angka pemutus arus hubung singkat | kaping | 30 |
12 | urip mekanik | kaping | 10000 |
13 | voltase kontrol mekanisme | ING | AC/DC220 |
14 | sirkuit secondary 1min frekuensi daya tahan voltase | kV | 2 |
15 | jarak reresik antarane kontak mbukak | mm | 16±1 |
16 | liwat lelungan | mm | 4±0.5 |
17 | kacepetan mbukak | m/s | 1.4-1.8 |
18 | kacepetan nutup | m/s | 0.4-0.8 |
19 | wektu bouncing nutup kontak | ms | ≤5 |
20 | telung phase mbukak / nutup asinkronisme | ms | ≤2 |
rong puluh siji | wektu nutup | ms | ≤100 |
rong puluh loro | wektu mbukak | ms | ≤50 |
telulikur | bobot | kg | 270 |
◆Sakabèhé Nggambar