Pemutus sirkuit vakum HV ruangan ZW7-40.5 yaiku peralatan switch ruangan 3-phase AC 50Hz 40.5kV.
♦ Cara instalasi: instalasi pondasi;
♦ Mekanisme operasi: mekanisme operasi spring lan mekanisme operasi elektromagnetik;
♦ Bahan kutub: karet silikon, keramik;
♦ Aplikasi: outdoor 33kV gardu, pembangkit listrik.
♦ Trafo saiki: instalasi ing-buit, instalasi njaba.
Standar Produk
♦ IEC62271-100 Switchgear Tegangan Tinggi lan Piranti Kontrol Bagean 100: Pemutus Sirkuit AC
♦ GB1984 High Voltage AC Circuit-breakers
♦ GB/T11022 Spesifikasi Umum kanggo Switchgear voltase dhuwur lan Standardgear Kontrol
♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers
♦ DL/T402 Spesifikasi Pemutus Sirkuit AC voltase dhuwur
Kondisi Lingkungan
♦ Suhu sekitar: -40°C~+40°C;
♦ Dhuwur:
♦ Kacepetan angin maksimal yaiku 10km/jam, kacepetan angin minimal kanggo tingkat sing dirating (132/230kv) yaiku 3,2km/jam;
♦ Intensitas lindhu:
♦ Jarak creepage nominal minimal: 31mm/kV;
♦ Tingkat polusi udara: Kelas IV.
Parameter Teknis Utama
Ora | Item | Unit | Nilai | |
1 | Dirating voltase | kV | 40.5 | |
Iku | Tingkat isolasi | Frekuensi daya 1 mnt Tes garing (fraktur, antar-fase, menyang bumi) Uji basah (menyang bumi, insulasi eksternal) | kV | 95 85 |
Impuls kilat tahan tegangan (puncak) | 185 | |||
3 | Rated saiki | A | 1250, 1600, 2000, 2500 | |
4 | Rated short circuit breaking saiki | kA | 20, 25, 31.5 |
Ora | Item | Unit | Nilai |
5 | Rated short circuit nggawe arus (puncak) | kA | 50, 63, 80 |
6 | Rated puncak tahan saiki | kA | 50, 63, 80 |
7 | Dirating wektu cendhak tahan saiki | kA | 20, 25, 31.5 |
8 | Rated urutan operasi | O-0.3S-CO-180S-CO | |
9 | Rated short circuit breaking saiki breaking number | kaping | 20 |
10 | Dirating short circuit duration | s | 4 |
11 | Wektu istirahat | s | ≤0.09 |
12 | Urip mekanik | kaping | 10000 |
13 | Interrupter vakum sing mentas diprodhuksi | Ps | ≤1.33×10-3 |
Interrupter vakum sajrone wektu panyimpenan 20 taun | -2 | ||
14 | Circuit breaker bobot net | kg | 800 |
15 | Clearance antarane kontak mbukak | mm | 22±2 |
16 | Kontak travel | mm | 4±1 |
17 | kacepetan mbukak rata-rata | m/s | 1.4-1.7 |
18 | Kacepetan nutup rata-rata | m/s | 0.4-0.7 |
19 | Kontak nutup wektu bouncing | ms | ≤3 |
20 | Sinkronisme pambuka lan penutupan antar fase | ms | ≤2 |
rong puluh siji | wektu nutup | ms | 50≤t≤200 |
rong puluh loro | wektu mbukak | ms | 30≤t≤60 |
telulikur | Saben fase sirkuit utama DC resistance (ora kalebu CT internal resistance) | mΩ | ≤100 |
patlikur | Kekandelan kumulatif kontak dinamis lan tetep diijini nganggo | mm | 3 |
25 | Tekanan kontak terukur | N | 2500±200 |
Gambar Struktur Umum lan Ukuran Instalasi (unit: mm)
♦Tipe mekanisme sisih