FN12-12 njero ruangan HV online mbukak ngalih break punika 3-phase AC 50Hz 12kV peralatan ngalih njero ruangan.
♦ Cara instalasi: dipasang ing ngarep, dipasang ing sisih, dipasang flip;
♦ Mekanisme operasi: mekanisme operasi spring, jinis manual lan jinis listrik kasedhiya;
♦ Jinis operasi: operasi tengen lan operasi kiwa;
♦ Aplikasi: switchgear 12kv njero ruangan.
Kondisi Lingkungan
♦ Suhu sekitar: -25°C~+40°C;
♦ Altitude:
♦ Kelembapan relatif: rata-rata saben dina
♦ Intensitas lindhu:
♦ Tingkat polusi: II;
♦ Panggonan tanpa geni, bledosan, korosi kimia lan getaran serius.
Parameter Teknis Utama
NO | Item | Unit | FN12-12D/6 30-20 | FN12-12RD/1 25-31.5 | ||
1 | Dirating voltase | kV | 12 | 12 | ||
2 | Frekuensi dirating | Hz | 50 | 50 | ||
3 | Rated saiki | A | 630 | 125 | ||
4 | 1 min frekuensi daya tahan voltase (Fase kanggo bumi, antarane kutub, kontak mbukak) | Phase-to-earth, phase-to-phase | kV | 42 | 42 | |
Isolasi fraktur | 48 | 48 | ||||
5 | Tegangan tahan impuls kilat sing dirating (Fase menyang bumi, antarane kutub, kontak mbukak) | Phase-to-earth, phase-to-phase | kV | 75 | 75 | |
Isolasi fraktur | 85 | 85 | ||||
6 | Dirating wektu cendhak tahan saiki (arus stabilitas termal) | Ngalih istirahat mbukak | kA | 20 | ||
Ngalih bumi | 20 | |||||
7 | Dirating durasi sirkuit cendhak (wektu stabilitas termal) | Ngalih istirahat mbukak | s | 4 | ||
Ngalih bumi | 2 | |||||
8 | Rated short circuit nggawe arus (puncak) | kA | 50 | |||
9 | Rated breaking saiki | Arus beban aktif | A | 630 | ||
Loop breaking saiki | 630 | |||||
5% beban aktif breaking saiki | 31.5 | |||||
Arus pengisian kabel | 10 | |||||
Kapasitas trafo tanpa beban | kVA | 1250 | ||||
10 | Rated short circuit breaking current (limit current fuse) | kA | 31.5 | |||
11 | Rated transfer saiki | A | 1200 | |||
12 | Urip mekanik | kaping | 2000 | 2000 | ||
13 | Energi output striker | J | 1±0.5 |
Gambar Struktur Umum lan Ukuran Instalasi (unit: mm)
♦ FN12-12D (operasi sisih kiwa dipasang)
♦ FN12-12D (operasi kiwa dipasang flip)
♦ FN12-12RD (operasi kiwa dipasang ing sisih ngarep)
♦ FN12-12RD (ngarep flip-dipasang operasi kiwa)