Pemutus sirkuit vakum voltase dhuwur VS1-12 yaiku switchgear njero ruangan kanggo tegangan AC 50Hz telung fase sistem tenaga 12kV, minangka unit perlindungan lan kontrol kanggo peralatan listrik peralatan kothak lan perusahaan industri lan pertambangan. Cocog kanggo operasi sing kerep miturut arus kerja sing dirating, utawa kanggo papan ing ngendi arus short-circuit rusak dening sawetara nyebrang.
Pemutus sirkuit nggunakake desain mekanisme operasi lan awak pemutus sirkuit, sing bisa digunakake minangka unit instalasi tetep utawa unit sing bisa ditarik.
VS1-12 pemutus sirkuit vakum HV njero ruangan yaiku peralatan ngalih njero ruangan AC 50Hz 12kV 3 fase.
♦ Cara instalasi: jinis withdrawable, jinis tetep, jinis dipasang ing sisih;
♦ Mekanisme operasi: mekanisme rating spring ope, mekanisme operasi magnet permanen;
♦ Jinis kutub: kutub sing dipasang, kutub sing dipasang;
♦ Aplikasi: switchgear KYN28-12, XGN-12.
♦ Steker sekunder: 58 pin, 64 pin.
Standar Produk
♦ IEC62271-100 Switchgear Tegangan Tinggi lan Piranti Kontrol Bagean 100: Pemutus Sirkuit AC
♦ GB1984 High Voltage AC Circuit-breakers
♦ GB/T11022 Spesifikasi Umum kanggo Switchgear voltase dhuwur lan Standardgear Kontrol
♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers
♦ DL/T402 Spesifikasi Pemutus Sirkuit AC voltase dhuwur
Kondisi Lingkungan
♦ Suhu sekitar: -15°C~+40°C;
♦ Dhuwur:
♦ Kelembapan relatif: rata-rata saben dina
♦ Intensitas lindhu:
♦ Panggonan tanpa geni, bebaya bledosan, reged serius, korosi kimia, uga geter kuat.
Parameter Teknis Utama
Ora | Item | Unit | Nilai |
1 | Dirating voltase | kV | 12 |
2 | 1 min frekuensi daya tahan voltase | 42 | |
3 | Rated kilat impuls tahan voltase | 75 | |
4 | Frekuensi dirating | Hz | 50 |
5 | Rated saiki | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 |
6 | Rated short circuit breaking saiki | kA | 20, 25, 31.5, 40 |
7 | Dirating wektu cendhak tahan saiki | 20, 25, 31.5, 40 | |
8 | Dirating short circuit duration | s | 4 |
9 | Nilai puncak sing dirating tahan arus | kA | 50, 63, 80, 100 |
10 | Rated short circuit nggawe saiki | 50, 63, 80, 100 | |
11 | Frekuensi daya sirkuit sekunder tahan voltase (1 menit) | ING | 2000 |
12 | Rated single / back-to-back kapasitor bank breaking saiki | A | 630/400 (800/400 kanggo 40kA lan 50 kA) |
Ora | Item | Unit | Nilai |
13 | Rated kapasitor bank nutup arus inrush | A | 12.5 |
14 | Wektu mbukak (voltase dirating) | ms | 20-50 |
15 | Wektu nutup (voltase dirating) | ms | 35-70 |
16 | Urip mekanik | kaping | 10000 |
17 | Dirating nomer breaking saiki | kaping | 10000 |
18 | Rated short circuit saiki breaking nomer | kaping | 50 (30 kanggo 40kA;20 kanggo 50kA) |
19 | Obah lan tetep kontak kumulatif diijini nyandhang kekandelan | mm | 3 |
20 | Rated voltase nutup operasi | ING | AC/DC110/220 |
rong puluh siji | Rated mbukak voltase operasi | ||
rong puluh loro | Dirating voltase saka motor panyimpenan energi | ING | 70 (80 ror 40kA lan 50kA) |
telulikur | Dirating daya motor panyimpenan energi | ||
patlikur | Wektu panyimpenan energi | s |
|
25 | Clearance antarane kontak mbukak | mm | 11±1 |
26 | liwat lelungan | mm | 3,5 ± 0,5 |
27 | Kontak nutup wektu bouncing | ms | ≤2 (≤3 kanggo 40kA lan 50kA) |
28 | Asynchronism mbukak lan nutup telung phase | ms | ≤2 |
29 | kacepetan mbukak rata-rata | m/s | 0.9-1.2 |
30 | Kacepetan nutup rata-rata | m/s | 0.5-0.8 |
31 | Resistansi sirkuit konduktif utama | mΩ | ≤60 (630A) ≤50 (1250A) ≤35 (1600-2000A) ≤25 (ndhuwur 2500A) |
32 | Tekanan kontak tutup kontak | N | 2000±200(20kA) 2400±200(25kA) 3100±200 (31.5kA) 4250±250 (40kA) 6500±500 (50kA) |
33 | Rated urutan operasi | O-0.3s-CO-180s-CO O-180s-CO-180s-CO (50kA) |