Produk anyar kita, NVS1-12 seri njero ruangan vakum voltase dhuwur mbobol sirkuit digunakake kanggo switchgears ing sistem daya 12kV, minangka kontrol lan pangayoman unit saka peralatan electrical ing Enterprises industri lan pertambangan, pembangkit listrik lan gardu. Amarga kaluwihan khusus saka mbobol sirkuit vakum, iku utamané cocok kanggo operasi Kerep mrintahake saiki digunakake, utawa panggonan ngendi short-circuit saiki bejat kaping pirang-pirang. Pemutus sirkuit nggunakake desain terpadu mekanisme operasi lan awak pemutus sirkuit. Loro kasebut minangka struktur ngarep lan mburi, sing nduweni fungsi interlocking sing dipercaya. Pemutus sirkuit bisa digunakake minangka unit instalasi tetep. Uga bisa dilengkapi truk sasis menyang unit gerobak tangan.

 

standar produk

GB / T1984-2014 High voltase AC Circuit Breaker

JB/T3855-2008 3.6-40.5kV njero ruangan AC tegangan Tinggi vakum pemutus sirkuit

DL/T403-2000 12kV-40.5kV tegangan tinggi pemutus sirkuit vakum pesenan kondisi teknis

IEC62271-100: 2008 Switchgear Tegangan Tinggi lan Piranti Kontrol Bagean 100: Pemutus Sirkuit AC

 

Kondisi Lingkungan

Suhu sekitar: -15 C ~ + 40 C

O Kelembapan sekitar: Kelembapan relatif rata-rata saben dina

Tekanan uap rata-rata saben dina

O Altitude ≤ 1000m;

O Intensitas lindhu

O Panggonan Instalasi: Titik kudu ora ana bebaya waterlosion, polusi serius, karat kimia lan goyang kepileh.

 

Parameter Teknis Utama

Item Unit data
Dirating voltase kV 12
Frekuensi dirating Hz 50
Rated 1 min frekuensi daya tahan voltase (phase kanggo phase, kanggo bumi, fraktur) kV 42
Rated lightning impulse tahan voltase (phase to phase, to earth, fraktur) kV 75
Urutan operasi sing dirating   Ot-APA-T'-APA

 

Item Unit

NVS1-12

Rated saiki A 630 1250 1250 1600 2000 2500 1250 1600 2000 2500 3150 3150 4000
Rated short circuit breaking saiki kA 20/25 31.5 40 50
Rated short circuit nggawe arus (puncak) kA 50/63 80 100 125
Dirating durasi saka short circuit s 4 4 4 4
Dirating short circuit breaking kaping wektu 50 50 30 20
Urip mekanik wektu 20000 20000 20000 10000

 

Cathetan:

20/25/31.5kA, t=0.3s t'=180s

40/50kA, t=180s, t'=180s

4000A VCB perlu cooling online dipeksa

 

Item Unit data
Clearance antarane kontak mbukak mm 9±1
Overtravel 3,5 ± 0,5
Asynchronism mbukak lan nutup telung phase ms ≤2
Kontak nutup wektu bouncing ms ≤2 (50kA)
Tekanan kontak kontak tutup N 20kA 25 kA 31,5 kA 40 kA 50 kA
2000±200 2400±200 3100±200 4250±250 5500±300
kacepetan mbukak rata-rata m/s 0.9~1.3
Kacepetan nutup rata-rata 0.4~0.8

 

Gambar Struktur Umum lan Ukuran Instalasi (unit: mm)

 

1 NVS1 dimensi1 1 NVS1 dimensi 2 1 NVS1 dimensi3

NVS1 ukuran 4

 