NVS1-24 Series Indoor High Voltage Vacuum Circuit Breaker

Katrangan singkat:


Detail Produk

Tag produk

Ringkesan

Produk anyar kita, NVS1-24 seri njero ruangan vakum voltase dhuwur mbobol sirkuit digunakake kanggo switchgears ing sistem daya 24kV, minangka kontrol lan pangayoman unit saka peralatan electrical ing Enterprises industri lan pertambangan, pembangkit listrik lan gardu. Amarga kaluwihan khusus saka mbobol sirkuit vakum, iku utamané cocok kanggo operasi Kerep mrintahake saiki digunakake, utawa panggonan ngendi short-circuit saiki bejat kaping pirang-pirang. Pemutus sirkuit nggunakake desain terpadu mekanisme operasi lan awak pemutus sirkuit. Loro kasebut minangka struktur ngarep lan mburi, sing nduweni fungsi interlocking sing dipercaya. Pemutus sirkuit bisa digunakake minangka unit instalasi tetep. Uga bisa dilengkapi truk sasis menyang unit gerobak tangan.

 

standar produk

GB / T1984-2014 High voltase AC Circuit Breaker

JB/T3855-2008 3.6-40.5kV njero ruangan AC tegangan Tinggi vakum pemutus sirkuit

DL/T403-2000 12kV-40.5kV tegangan tinggi pemutus sirkuit vakum pesenan kondisi teknis

IEC62271-100: 2008 Switchgear Tegangan Tinggi lan Piranti Kontrol Bagean 100: Pemutus Sirkuit AC

 

Kondisi Lingkungan

Suhu sekitar: -15 C ~ + 40 C

O Kelembapan sekitar: Kelembapan relatif rata-rata saben dina

Tekanan uap rata-rata saben dina

O Altitude ≤ 1000m;

O Intensitas lindhu

O Panggonan Instalasi: Titik kudu ora ana banyu, bebaya bledosan, polusi serius, korosi kimia lan goyang sing apik banget.

 

Parameter Teknis Utama

Item

Unit

data

Dirating voltase

kV

patlikur

Frekuensi dirating

Hz

50

Rated 1 min frekuensi daya tahan voltase (phase kanggo phase, kanggo bumi, fraktur)

kV

65

Rated lightning impulse tahan voltase (phase to phase, to earth, fraktur)

kV

125

Urutan operasi sing dirating

 

Ot-APA-T'-APA

 

 

Item

Unit

NVS1-24

Rated saiki

A

630

1250

1250

1600

2000

2500

1250

1600

2000

2500

3150

Rated short circuit breaking saiki

kA

20/25

31.5

40

Rated short circuit nggawe arus (puncak)

kA

50/63

80

100

Dirating durasi saka short circuit

s

4

4

4

Dirating short circuit breaking kaping

wektu

50

50

30

Urip mekanik

wektu

20000

20000

20000

Cathetan:

20/25/31.5kA, t=0.3s t'=180s

40/50kA, t=180s, t'=180s

4000A VCB perlu cooling online dipeksa

 

Item

Unit

data

Clearance antarane kontak mbukak

mm

13±1

Overtravel

3,5 ± 0,5

Asynchronism mbukak lan nutup telung phase

ms

≤2

Kontak nutup wektu bouncing

ms

≤ 3 (50kA)

Tekanan kontak kontak tutup

N

20kA

25 kA

31,5 kA

40 kA

50 kA

2000±200

2400±200

3100±200

4250±250

5500±300

kacepetan mbukak rata-rata

m/s

1.1~1.6

Kacepetan nutup rata-rata

0.6~1.0

 

Gambar Struktur Umum lan Ukuran Instalasi (unit: mm)