Ringkesan
Produk anyar kita, NVS1-24 seri njero ruangan vakum voltase dhuwur mbobol sirkuit digunakake kanggo switchgears ing sistem daya 24kV, minangka kontrol lan pangayoman unit saka peralatan electrical ing Enterprises industri lan pertambangan, pembangkit listrik lan gardu. Amarga kaluwihan khusus saka mbobol sirkuit vakum, iku utamané cocok kanggo operasi Kerep mrintahake saiki digunakake, utawa panggonan ngendi short-circuit saiki bejat kaping pirang-pirang. Pemutus sirkuit nggunakake desain terpadu mekanisme operasi lan awak pemutus sirkuit. Loro kasebut minangka struktur ngarep lan mburi, sing nduweni fungsi interlocking sing dipercaya. Pemutus sirkuit bisa digunakake minangka unit instalasi tetep. Uga bisa dilengkapi truk sasis menyang unit gerobak tangan.
standar produk
GB / T1984-2014 High voltase AC Circuit Breaker
JB/T3855-2008 3.6-40.5kV njero ruangan AC tegangan Tinggi vakum pemutus sirkuit
DL/T403-2000 12kV-40.5kV tegangan tinggi pemutus sirkuit vakum pesenan kondisi teknis
IEC62271-100: 2008 Switchgear Tegangan Tinggi lan Piranti Kontrol Bagean 100: Pemutus Sirkuit AC
Kondisi Lingkungan
Suhu sekitar: -15 C ~ + 40 C
O Kelembapan sekitar: Kelembapan relatif rata-rata saben dina
Tekanan uap rata-rata saben dina
O Altitude ≤ 1000m;
O Intensitas lindhu
O Panggonan Instalasi: Titik kudu ora ana banyu, bebaya bledosan, polusi serius, korosi kimia lan goyang sing apik banget.
Parameter Teknis Utama
Item | Unit | data |
Dirating voltase | kV | patlikur |
Frekuensi dirating | Hz | 50 |
Rated 1 min frekuensi daya tahan voltase (phase kanggo phase, kanggo bumi, fraktur) | kV | 65 |
Rated lightning impulse tahan voltase (phase to phase, to earth, fraktur) | kV | 125 |
Urutan operasi sing dirating |
| Ot-APA-T'-APA |
Item | Unit | NVS1-24 | ||||||||||
Rated saiki | A | 630 | 1250 | 1250 | 1600 | 2000 | 2500 | 1250 | 1600 | 2000 | 2500 | 3150 |
Rated short circuit breaking saiki | kA | 20/25 | 31.5 | 40 | ||||||||
Rated short circuit nggawe arus (puncak) | kA | 50/63 | 80 | 100 | ||||||||
Dirating durasi saka short circuit | s | 4 | 4 | 4 | ||||||||
Dirating short circuit breaking kaping | wektu | 50 | 50 | 30 | ||||||||
Urip mekanik | wektu | 20000 | 20000 | 20000 |
Cathetan:
20/25/31.5kA, t=0.3s t'=180s
40/50kA, t=180s, t'=180s
4000A VCB perlu cooling online dipeksa
Item | Unit | data | ||||
Clearance antarane kontak mbukak | mm | 13±1 | ||||
Overtravel | 3,5 ± 0,5 | |||||
Asynchronism mbukak lan nutup telung phase | ms | ≤2 | ||||
Kontak nutup wektu bouncing | ms | ≤ 3 (50kA) | ||||
Tekanan kontak kontak tutup | N | 20kA | 25 kA | 31,5 kA | 40 kA | 50 kA |
2000±200 | 2400±200 | 3100±200 | 4250±250 | 5500±300 | ||
kacepetan mbukak rata-rata | m/s | 1.1~1.6 | ||||
Kacepetan nutup rata-rata | 0.6~1.0 |
Gambar Struktur Umum lan Ukuran Instalasi (unit: mm)